This type of Isolated Safety Barrier transmits thermocouple signals from hazardous area to safe area by isolating transmitting current or voltage signals in a circuit or two isolated circuits, the input, output, and power supply are galvanically isolated from each other. Besides, it may also be connected in a connection network in safe area via communication ports. It is an intelligent product with online self-diagnosis function. Customer may set the type and the range of the input or output signals with a handheld programmer we provide.
Dielectric strength:
≥2500V AC (Input/Output/Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply:
18~32V DC (Recommended voltage:24V DC)
Power consumption:
0.5W (24V power supply, 20mA single output)
0.7W (24V power supply, 20mA double output)
Mainly Technical Parameters:
Explosive-proof grade: [Ex ia]ⅡC
Permissible input signal from hazardous area:
Thermo-couple:K, E, S, B, J, T, R, N
Signal type and range can be specified at your order and may also be programmed by user.
Output signal to safe area:
DC current:0~10 mA, 4~20 mA, 0~20 mA
DC voltage:0~5 V, 1~5 V, 0~10 V
Signal type and range can be specified at your order and may also be programmed by user.
Transmitting accuracy(at 25℃±2℃, without temperature compensation):
TC type | Measurable range | Accuracy |
K/E/J/N etc. | < 300 ℃ | ±0.3 ℃ |
≥ 300℃ | ±0.1% F∙S | |
S/B/T/R/WRe-series | < 500 ℃ | ±0.5 ℃ |
≥ 500 ℃ | ±0.1% F∙S |
Influence of ambient temperature: < 30 ppm/℃
Rise time: ≤ 2 s (bounce from 10%~90%)
Output load capacity:
DC current:0~10mA: 0~700 Ω;4~20mA: 0~350 Ω
DC voltage: 0(1) ~ 5V: ≥ 1 MΩ; 0~10V: ≥ 2M Ω
Cold junction compensation range:-20℃~+60℃
Cold junction compensation accuracy:
±1℃ (Preheated for 10 minutes).
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products (CQST):
Um =250VAC/DC
Between terminal 1 & 2, 4 & 5:
Uo=6.5 V, Io=9.7 mA, Po=15.8 mW
ⅡC: Co=17.5 μF, Lo=264 mH
ⅡB: Co=399 μF, Lo=792 mH
ⅡA: Co=700 μF, Lo=1000 mH
Model Indication:
Model | Note | ||||
NPEXA-C1 | ╳ | ╳ | ╳ | ╳ | Thermo-couple input isolated safety barrier |
Input loop |
|
|
|
| Single loop as default |
D |
|
|
| Double loop | |
1st output | 1 |
|
| 4~20mA | |
2 |
|
| 1~5V | ||
3 |
|
| 0~10mA | ||
4 |
|
| 0~5V | ||
5 |
|
| 0~10V | ||
6 |
|
| 0~20mA | ||
2nd output |
|
| None as default | ||
1 |
| 4~20mA | |||
2 |
| 1~5V | |||
3 |
| 0~10mA | |||
4 |
| 0~5V | |||
5 |
| 0~10V | |||
6 |
| 0~20mA | |||
Communication OR Alarm function |
| None as default | |||
T1 | 485 communication (single output only) | ||||
T2 | 232 communication (single output only) | ||||
A1 | Single relay alarm output | ||||
A2 | Double relay alarm output |
Note:
Thermocouple input type and the corresponding output range need to be specified when placing order. If you needs to program by yourself, please operate with computer or a handheld programmer.